The CO₂ calculator sizes enrichment properly: how much gas it takes to lift a room to target, how much leaks away every hour, how long a bottle lasts, and what light intensity the concentration actually justifies.
Formula — CO₂ calculator
CO₂ demand has two parts — the one-off charge that lifts the room from ambient to target, and a continuous make-up flow that replaces what leaks out. Density comes from the ideal gas law rather than a fixed constant, because it drops from 1.83 kg/m³ at 20 °C to 1.80 kg/m³ at 25 °C.
- density [kg/m³] = (101325 × 0.04401) ÷ (8.314 × (T + 273.15))
- Δppm = target − ambient
- pure CO₂ volume [m³] = room volume × Δppm × 10⁻⁶
- mass per fill [g] = CO₂ volume × density × 1000
- make-up [g/h] = mass per fill × leakage ACH
- per day [g] = mass per fill + make-up × dosing hours
- propane [kg] = CO₂ [kg] ÷ 3.0 (and 46.3 MJ of heat per kg burned)
- Leakage ACH by build: sealed 0.25, tight 0.5, average 1.0, leaky 2.0.
- Practical plant ceiling 1500 ppm; the 8-hour human exposure limit is 5000 ppm.
Worked example — CO₂ calculator
A 120 × 120 × 200 cm room holds 2.88 m³. Lifting it from 420 ppm to 1200 ppm is a Δ of 780 ppm, which is 2.88 × 780 × 10⁻⁶ = 0.00225 m³ of pure CO₂. At 25 °C (1.80 kg/m³) that is about 4.0 g per fill — a trivial amount, which is why the running loss dominates.
With an average-tightness room (1.0 ACH) the make-up demand is also ≈4.0 g/h. Dosing for 12 h a day costs 4.0 + 4.0 × 12 ≈ 52 g/day, or about 4.7 kg over a 90-day run. A 10 kg bottle therefore lasts roughly 190 days of dosing — two full grows. Sealing the same room to 0.5 ACH halves the make-up and takes the season down to about 2.5 kg. Generating that CO₂ by burning propane instead would need ≈1.6 kg of gas and release about 73 MJ of extra heat, which is why burners belong in cold rooms with real cooling capacity.
Typical ranges — CO₂ calculator
Enrichment only pays off when light, temperature and nutrition are already at the top of their bands. Below about 600 PPFD, extra CO₂ changes almost nothing; above 1000 PPFD it is often the limiting factor. Never dose a room people work in without ventilation interlocks and a monitor.
| Parameter | Usual range |
|---|---|
| Ambient CO₂ | 400–450 ppm outdoors, 500–800 ppm in an occupied house |
| Enrichment target | 800–1200 ppm; 1500 ppm is the practical ceiling |
| Useful PPFD at 400 ppm | 600–900 µmol/m²/s |
| Useful PPFD at 1200 ppm | 1200–1400 µmol/m²/s |
| Season consumption, 1.2 m² room | 2–6 kg of bottled CO₂ |
| Dosing window | lights-on hours only — plants fix no carbon in the dark |